Descrizione
Data sheet 05/10-365-6
Emergency lighting units
EM series
Product description
• Emergency lighting supply unit for manual testing
• For linear and compact fluorescent lamps
• Low-profile casing (21 x 30 mm cross-section)
Properties
• 1 or 3 h rated duration
• Compatible with all electronic ballasts
(dimmable and non-dimmable)
• 5-pole technology: 4-pole lamp changeover
and delayed power switching for the ballast
• High-frequency ac operation of the lamp
• Hot restart in emergency mode
• Gentle on the lamp thanks to permanent
cathode heating in emergency mode
• 55 sec. boost start for rapid heating of the lamp, more
light in the startup phase and optimum lamp life
• Maximum ballast lumen factors (BLF) for all lamps
• Green charge status display LED
• Electronic multi-level charge system
• Deep discharge protection
• Short-circuit-proof battery connection
• Polarity reversal protection for battery
Batteries
• High-temperature cells
• NiCd or NiMH batteries
• D or Cs cells
• Blade terminals for simple connection
È
Standards, page 6
Wiring diagrams and installation examples, page 8
EM BASIC lp, 220 – 240 V
BASIC versionT5cTC-DDTC-F
TC-L
TC-DEL
TC-SEL
TC-TEL
T8T5
Technical data
Rated supply voltage 220 – 240 V
Mains frequency 50 / 60 Hz
Mains current 60 mA
Rated power < 10 W
Overvoltage protection 320 V (for 1 h)
Maximum operating voltage (U-OUT of the ECG) 460 V
Battery charging time 3 / 1 h 15 / 10 h
Discharge current 1.1 A
Leakage current (PE) 0.5 mA
Ambient temperature ta -5 … +60 °C
Max. casing temperature tc 70 °C
Mains voltage changeover threshold according to EN 60598-2-22
Min. lamp starting temperature (emergency operation) -5 °C
Type of protection IP20
Protection class I